Shopping Basket

0 Items

Subtotal £0.00

Kidde NC Series 2-8 Zone Conventional Fire Panel

£200.26£283.11

SKU: NC-PF Category: Brand:

Summary

The Kidde NC-PF is a state-of-the-art conventional fire control panel designed for small to mid-sized applications. Its contemporary design seamlessly integrates into any decor, while the intuitive user interface with icons ensures ease of use without the need for additional language kits. This panel supports multiple lines of conventional detectors and accessories, making it a versatile solution for building owners and installation/maintenance companies.

With two, four or eight zones capable of supporting up to 32 devices each, the NC-PF2 offers robust functionality, including supervised relay outputs for sounder control and user-configurable inputs for monitoring and control. Its modern features and compliance with various standards make it a reliable choice for fire safety management.

Features

  • Modern and elegant design
  • Easy removable parts for installation
  • Supervised alarm notification outputs
  • Auxiliary 24 VDC supply output with reset support
  • Default support for special functions
  • Two types of auxiliary relay boards for expanded outputs
  • Normal, head-out & intrinsically safe zone support
  • Full front panel diagnostics
  • One-man walk test and CleanMe™ function

Specifications

  • Maximum System Capacity (Device Count) : Up to 1280
  • Operating Temperature : -5 to +50°C
  • Storage Temperature : -20 to +70°C
  • Network Size (Nodes) : Up to 32
  • Relative Humidity : 10 to 95% Non-Condensing
  • Environment : Indoor
  • IP Rating : IP30
  • Power Supply Type : VAC
  • Power Consumption : 2 A @ 24 VDC
  • Operating Voltage : 110 VAC @ 50 Hz or 230 VAC @ 50 Hz (+10% -15%)
  • Cable Type : 3 x 1.5 mm² (Live, Neutral, Earth)
  • Compliancy : CPD, RoHS, WEEE
  • Certification : EN54-2, EN54-4
  • Current Consumption : 2 A @ 110/240 VAC
  • Auxiliary Supply Output Load (Max.) : 250 mA @ 25°C / 195 mA @ 40°C
  • Maximum Loop Capacity : 2
  • Maximum Zone Capacity : Up to 2
  • Operating Voltage (Zone) : 22 VDC (18 to 24 VDC)
  • Quantity of Devices per Zone : 32 Max.
  • Rating : 65 mA (Max. Load)
  • Cable Rating : 40 Ohm (Max Cable Resistance), 500 nF (Max Cable Capacitance)
  • Input Quantity : 2
  • Input Type and Rating : 100 Ohm (Max. Cable Resistance)
  • Supervisory Voltage : -15 to +28 VDC
  • Auxiliary Power : 24 VDC (21 to 28 VDC)
  • Supervised Outputs : 2
  • Load (Max.) : 250 mA
  • Non-Supervised Outputs: 2
  • Load : 2 A @ 30 VDC
  • Standby Battery Capacity : 2 x 12 V, 7.2 Ah (SLA)
  • Physical Dimensions : 320 x 435 x 134 mm (W x H x D)
  • Net Weight : 2.8 kg (Without Battery)
  • Shipping Weight : 4.5 kg
  • Colour : Grey (RAL 7035)
  • Mounting Type : Surface Mount
  • Cable Entries : Ø 20 mm – 14 / 2 / 12 (Top / Bottom / Rear)

Downloads

Datasheets

Additional information

Device Type

Zones

2, 4, 8