Fike Twinflex Input Output (I/O) Module

£47.08 (inc VAT: £56.50)

In Stock

SKU: 802-0006 Category: Brand:

Summary

  • Provides an interface between ancillary equipment and Twinflex zone
  • Can be configured as an input for another system
  • Zone powered
  • Mains rated relay contacts

Specifications

  • Dimensions:
    • Overall: 146 x 87x 41mm
    • Back box: 146 x 87 x 32mm
  • Operating temperature: -10°C to +45°C
  • Voltage Ranges:
    • DC Output from Mains Powered Panel: 25.5 to 35V DC
    • DC Output from Battery Powered Panel: 20 to 26V DC
  • Operating Current (Typical):
    • Quiescent: 0.207 mA
    • End of line ON if applicable: 0.080 mA (in addition to Quiescent)
    • Active: 22.715 mA
  • LED Indication:
    • Output Active LED (Red): On continuously when output active
    • Status – EOL/Input Active LED (Red):
      • On continuously when input active
      • Flash once every 20 secs for normal
      • Flash once every 5 secs for EOL
  • Max Cable Length to Input: 3 Metres
  • Contact Rating:
    • DPCO Relay Max load:
      • 30V DC ⎓ 2A
      • 250V AC 50Hz/60Hz 2A
      • Max 3A Surge
  • Fuses:
    • Fuse 1, Fuse 2:
      • 3.15A Antisurge 20mm Ceramic
      • 250V AC (eg. Bussman S505-3.15A)
  • Loading Units (Pro Panel):
    • Max Loading Units per Zone: 160 DLU
    • I/O Unit: 23 DLU
  • Flammability: UL94-V2
  • IP Rating: IP 30

Downloads

Additional information

Weight 0.4 kg