Fike Twinflex Input Output (I/O) Module
£47.08 (inc VAT: £56.50)
Summary
- Provides an interface between ancillary equipment and Twinflex zone
- Can be configured as an input for another system
- Zone powered
- Mains rated relay contacts
Specifications
- Dimensions:
- Overall: 146 x 87x 41mm
- Back box: 146 x 87 x 32mm
- Operating temperature: -10°C to +45°C
- Voltage Ranges:
- DC Output from Mains Powered Panel: 25.5 to 35V DC
- DC Output from Battery Powered Panel: 20 to 26V DC
- Operating Current (Typical):
- Quiescent: 0.207 mA
- End of line ON if applicable: 0.080 mA (in addition to Quiescent)
- Active: 22.715 mA
- LED Indication:
- Output Active LED (Red): On continuously when output active
- Status – EOL/Input Active LED (Red):
- On continuously when input active
- Flash once every 20 secs for normal
- Flash once every 5 secs for EOL
- Max Cable Length to Input: 3 Metres
- Contact Rating:
- DPCO Relay Max load:
- 30V DC ⎓ 2A
- 250V AC 50Hz/60Hz 2A
- Max 3A Surge
- DPCO Relay Max load:
- Fuses:
- Fuse 1, Fuse 2:
- 3.15A Antisurge 20mm Ceramic
- 250V AC (eg. Bussman S505-3.15A)
- Fuse 1, Fuse 2:
- Loading Units (Pro Panel):
- Max Loading Units per Zone: 160 DLU
- I/O Unit: 23 DLU
- Flammability: UL94-V2
- IP Rating: IP 30
Downloads
- Installation Manual (Adobe PDF)
Additional information
Weight | 0.4 kg |
---|