Haes AOV Smoke Vent Control Panel
Summary
The AOV control panel range has been developed to provide a comprehensive solution to smoke ventilation system control. Models include; 3 amp, 5 amp & 10 amp PSU versions for control of small, medium and larger loads.
Developed utilising the same detection circuit technology as our EN54 approved fire control panels the AOV offers a wide range of peripheral connections for the installer to utilise. The high spec models include all the available inputs and outputs in a single, off the shelf unit. No additional modules or cards are required.
Features
- Single zone conventional or Twin Wire detection circuit
- Vent status indications & controls
- 3A, 5A or 10A integral PSU
- High spec versions include all available inputs & outputs in a single, off the shelf unit (see Technical Specification)
- False alarm management mode included in all models
FAQ
Are the trigger resistors included with these AOV panels?
No.
I need a replacement controls enabled key, is this available?
Unfortunately this key is no longer available however the SWK134-WIRED is a compatible keyswitch assembly, including keys, which is compatible.
Specifications
- Main Features
- 3, 5 or 10 Amp PSU/ battery charger
- Space for up to 3.2Ah batteries (AOV-3)
- Space for up to 12Ah batteries (AOV-5/10)
- 1 Amp magnetic vent control output
- 1 x 5A timed polarity reversal actuator control outputs (AOV-3)
- 2 x 5A timed polarity reversal actuator control outputs (AOV-5/10)
- Alarm relay change over contacts
- Fault relay change over contacts (fail safe)
- Trigger input (monitored)
- Smoke detector input (conventional or Twin wire operation)
- False alarm mode
- Vent control switch inputs , Open / Close
- Fireman’s control switch inputs for On/Off, Auto setting. Disable & test modes
- Vent status indications & controls on front
- 12v dc output (100ma) for PIR power
- Additional Features for High Spec Version
- Rain sensor input (monitored)
- PIR sensor input (monitored)
- 0/10 V Positional control input 10% steps
- 0/10v Positional data output
- External Indications
- Vent Open
- Vent Closed
- Trigger Status
- Detector Status
- Supply Healthy
- General Fault
- General Alarm
- Disabled
- Test Mode
- Rain Sensor Status
- PIR Status
- PSU Fault
- System Fault
- Access Status
- External Controls
- Keyswitch or code entry ‘activate controls’
- Colour coded buttons for controls and programming
- Button functions:
- Open Vent
- Close Vent
- Reset
- Code entry keys 1, 2, 3, 4
- DIL Switch Selectable Options
- Invert magnetic vent output
- Actuator power to continuous mode
- Set smoke to Twin Wire mode
- BMS 0/10v control
- Programmable Options
- Set access code
- Input circuit options
- Latching
- Short circuit to activate
- Detector removal monitoring
- False alarm mode selection
- Actuator time setting, 10 to 150 seconds
- Disable battery monitoring
- Cabinet
- Mild steel, lockable, 20mm knockouts
- Colour ref: Radon MW334E Interpon powdercoat
- AOV-3
- Back box = 300mmW x 250mmH x 80mmD
- Lid = 308mmW x 260mmH x 23mmD
- Max battery size = 2 x 3.2Ah, 12v, SLA
- AOV-5/10
- Back box = 450mmW x 300mmH x 110mmD
- Lid = 460mmW x 310mmH x 25mmD
- Max battery size = 2 x 12Ah, 12v, SLA
Downloads
- Brochure (Adobe PDF)
- Datasheet (Adobe PDF)
- Installation & Commissioning Manual (Adobe PDF)
Additional information
Weight | 5 kg |
---|---|
Internal PSU Rating | 3A, 5A, 10A |
Specification | Standard, High |
Related Products
-
Haes Replacement Keyswitch Assembly For Esento Evoque, Excel, Eclipse Esprint & Fusion
HaesKey Features
- Replacement / spare key and lock
- Ideal for Haes fire alarm panel doors
- Old part number: SWK107WIRED