Lexicomm ViLX-OSA Type A Fire Telephone Handset with Stainless Steel Finish
Summary
The ViLX-OSA is a Type A EVCS outstation compatible with the Lexicomm standalone and network systems.
The outstation is supplied in a brushed stainless finish with a high contrast red screen print with a rugged red telephone handset behind the push door.
A stainless steel bezel is available to allow the outstation to be semi-recessed into a wall reducing the need to stock flush and surface variants.
Suitability
The ViLX-OSA is a Type A outstation as defined in BS 5839-9:2021, and can be used as a fire telephone or a disabled refuge call point.
The Lexicomm outstations are designed for use by multidisability users, having high contrast signage in line with RNIB guidelines and an induction loop coil (to BSEN60118-4)in the handset.
Type A outstations are mainly for use by buildingmanagement, fire wardens and fire fighters. They should be located as described in BS 9999:2017 and Building RegulationsApproved Document B.
Mounting Instructions
The outstation should be mounted at a height of 1300 to 1400mm from to the centre line of the outstation to the floor to comply with the requirements of Building Regulations Document M (Access for the Disabled).
When flush mounting a cut out of 305mm by 155mm is recommended, the bezel slides over the box and is fixed on the wall using a suitable sealant or mastic.
If the outstation is to also to be used as a refuge point, suitable space must be allowed so the system can be used by a parked wheelchair.
Key Features
- Compact design
- Ruggedised handset
- High volume ringer
- Status LED
- 20mm cable gland knock-out
- Telecoil for hearing impaired users
- Full duplex operation
- Fully compliant to BS 5839-9:2021
- Magnetic push catch
- Stainless steel as standard
- Flush bezel available
Specifications
- Physical :
- Dimensions :
- Surface (HxWxD) : 300x150x105mm
- Bezel (HxWxD) : 350x200x1mm
- Cut-out (HxWxD) : 305x155x95mm
- Weight : 2.2 kg
- Material : Stainless Steel
- Finish : Brushed
- Dimensions :
- Outstation Cables :
- Type : Enhanced Fire Resistant
- Cores : 1 x 2 core radial 1mm or 1.5mm
- Distance : 500m from a compatible panel
- Standards Compliance :
- EMC :
- EN 55035:2017+A11:2020
- EN 55032:2015+A1:2020
- LVD : EN IEC62368-1:2020+A11:2020
- Product Family :
- BS 5839-9:2021 BS 9999:2017
- EN 60118-4:2015+A1:2018
- EMC :
- Part Numbers :
- Outstation : ViLX-OSA
- Bezel : ViLX-OBZ