VESDA-E VEA Addressable Multi-way Interface, Pre-wired & Pre-addressed
£2,475.29 – £3,524.71
Summary
Un-like traditional air sampling smoke detection units that only offer zonal indication, the VESDA-E VEA system is able to provide the user with up to 40 individual sampling point locations. To enable this unique feature requires input from the installer i.e. wiring and addressing of multiple loop powered interface units on-stie (up to 40 per VEA unit).
Eurofyre offer unique history, knowledge and experience with microbore aspirating smoke detection. Eurofyre are responsible for over 400+ microbore systems sold and installed in applications such as high-end residential, retail , data centres, petrochemical and nuclear. We have a unique understanding of the challenges of assembling and wiring a multi-way interface on-site i.e. difficult access, multiple trades working in the same area, insufficient workspace and limited tool availability.
Features
- Pre-wired OEM interface assembly
- Pre-addressed pipe relays as per client specification
- Supporting the major addressable fire alarm protocols
- Full functional and 24 hour soak test prior to delivery
- Easy installation reducing overall completion time
Specifications
- Supply Voltage: 18 to 30Vdc (24Vdc Nominal)
- Power Consumption @ 24VDC: Average Quiescent: 20mA; Average Alarm: 250mA
- Dimensions (W x H x D): 352.05mm x 340.5mm x 135.5mm
- Weight: 5.1 kg
- Operating Conditions:
- Ambient: 0°C to 39°C
- Tested to: 0°C to 49°C
- Humidity: 10% to 95% RH, non-condensing
- IP Rating: IP40 (not UL tested)
- Cable Access: 4 x 25 mm (1”) cable entries
Downloads
- Datasheet (Adobe PDF)
Additional information
Weight | 2 kg |
---|---|
No. of Interfaces | 17-way Interface, 22-way Interface, 32-way Interface, 42-way Interface |