Apollo XP95 Sounder Circuit Controller
£70.11 (inc VAT: £84.13)
Summary
The XP95 Sounder Control Unit with Isolator is used to control the operation of a zone of externally powered sounders and to report their status to Apollo compatible control equipment. This Sounder Circuit Controller can allow units to be operated continuously, or to be pulsed, 1 Second on, 1 Second off. The controller can also be synchronised with loop sounders.
Key Features
The Sounder Control Unit with Isolator allows sounders to be operated continuously or be pulsed, 1 second on, 1 second off. Sounders may be operated individually or in groups and, whichever address mode has been applied, may be synchronised when in pulsed operation.
An opto-coupled input is provided to monitor the state of the external power supply.
The Sounder Control Unit with Isolator is fitted with a bi-directional short-circuit isolator and will be unaffected by loop short-circuits on either loop input or output.
Specifications
- Loop Operating Voltage : 17V DC
- Maximum Loop Operating Voltage : 28V DC
Sounder Control Data:-
- Current Consumption, Loop, @ 24V
- Switch on Surge, Max 100ms : 2.6mA
- Quiescent, 10ohms EOL Fitted : 1.95mA
- Sounders Operated : 1.7mA
- Fault (Yellow LED On) : 3.6mA
- Sounder Line Short Circuit : 2.8mA
- Current Consumption, External Supply
- Relay Off
- 1mA @ 9V
- 3mA @ 32V
- Sounders and Red LED On
- 44mA @ 9V
- 47mA @ 32V
- Sounder Output Monitoring Voltage : 9-11V DC
- Maximum Sounder Circuit Voltage : 32V DC
- Maximum Sounder Circuit Current : 1A @ 30V DC
Isolator Data:-
- On Resistance : 0.2ohms
- Maximum Continuous Current : 1A
- Maximum Switching Current : 3A
- Maximum Load : 20 XP95 / Discovery Detectors
- Operating Tempurature : -20 to +70 Degrees Celcius
- Humidity : 0-95%
- IP Rating : 54