Advanced MXP-532 General Routing Interface
£215.53 (inc VAT: £258.64)
Summary
The MXP-532 general routing interface card is an optional module to provide monitored circuits to either fire/fault routing equipment or fire protection equipment for compliance with BS EN54-2: 1998 Clauses 7.9 and 8.9 and BS5839-1:2002.
Applications / Limitations
EN54-2 compliant routing interfaces providing monitored outputs to the fire alarm and routing circuits. Circuits are monitored for open and short circuit conditions in both normal and active mode – compliant with EN54-2 and BS5839-1: 2002 Clause 12.2.1a.
The outputs will drive relay coils with impedances of between 1kΩ and 5kΩ.
Key Features
- Two fire routing outputs are provided to differentiate between Call Point (MCP) and Automatic Detector (AFD) fire alarm signals if required.
- Outputs are monitored for open and short circuit wiring issues in both the quiescent and active states, and fault conditions reported on the panel (CIE) display/LED Indicators.
- Outputs are compatible with a wide range of routing equipment.
- Simple to install and configure.
- Monitored outputs.
- Wide range compatibility.
Specifications
- Output Circuit Specification : 24V DC active, 5V DC monitor
- Fire & Fault Outputs : 1.0mA monitor mode nominal, 5.0mA-25.0mA active (energised) mode dependent upon coil impendence, 40.0mA maximum short circuit
- Input Circuit Specification : 4x Monitored Input – EOL 10KΩ, operating resistor 470Ω
- Operating Voltage : 24V DC [Range 19-28V] from panel auxiliary Supply Output.
- Panel Loading :
- Standby, AC Mains Fail (Fault Output Off) : 43mA
- Quiescent State (Fault Output On) : 45mA +24mA (1KΩ coil), +5mA (5KΩ coil)
- All Inputs And Outputs Active : 48mA +72mA (1KΩ coils), +15mA (5kΩ coils)
- On-board Iindications : 6 x LED indicators for outputs active, communications and microprocessor heartbeat
- Operating Temperature : 0°C to 50°C
- Approvals : BS EN54-2: 1998
Downloads
- Datasheet (Adobe PDF)
Additional information
Weight | 0.25 kg |
---|