Apollo XP95 Input/Output Unit With Isolator
Summary
The Apollo XP95 Input/Output Unit provides a voltage-free, double pole changeover (DPCO) relay output, a single monitored switch input and an unmonitored, non-polarised opto-coupled input.
Features
- It can report fault, switch open and switch closed levels
- Three visible LED’s
- Loop-Powered
- Capable of switching up to 30V at 1A
Specifications
- Minimum Loop Operating Voltage In Normal Condition : 17V DC
- Maximum Loop Operating Voltage : 28V DC
- Maximum Current Consumption At 28V DC No Protocol
- Switch-On Surge, Max 150mx : 3.5mA
- Quiescent, 20Ω EOL Fitted : 1.25mA
- Switch Input Closed ‘Switch Closed’ LED On : 2.5mA
- Switch Input Closed (LED Disabled) : 1.5mA
- Any Other Condition (Max 2 LEDs On) : 3.5mA
- Relay Operated : 2mA
- Switch Input Monitoring Voltage (Open-Circuit Condition) : 9-11V DC
- Maximum Cable Resistance : 50Ω
- Opto-Coupled Input Maximum Voltage (Polarity Sensitive) : 35V DC
- Impedance : 10kΩ
- Relay Output Contact Rating (Inductive or Resistive) : 1A at 30V AC or DC
- Relay Output Wetting Current At 10mV DC : 10μA
- On Resistance : 0.2Ω
- Maximum Continuous Current : 1A
- Maximum Switching Current : 3A
- Maximum Load : 20 XP95/Discovery Detectors
- Operating Temperature : -20°C to +70°C
- Humidity (No Condensation) : 0-95%
- IP Rating : 54
Additional information
Weight | 0.3 kg |
---|