The CAST XFP 1 loop addressable panel is a powerful and cost-effective fire detection and alarm system designed by C-TEC. It is certified to EN54 parts 2, 4, and 13, and is available with C-TEC’s own CAST digital fire alarm system protocol.

Features

  • Powerful 40V 450mA loop driver allows the connection of up to 255 CAST devices
  • High-speed data transmission and two soft addressing options (automatic via the panel or manual via a handheld programmer)
  • Suitable for small to medium-sized stand-alone applications and larger, more sophisticated installations

Specifications

  • Approvals/certifications : LPCB certified to EN54-2 & 4 and Kiwa Telefication certified to EN54-13
  • Protocol/compatibility : C-TEC CAST
  • Mains supply : 230V 50/60Hz
  • Mains rated current : 350mA maximum
  • Internal power supply : 27Vdc nominal
  • Total output current limited to : 1.4A @ 230Vac (Imax.A 210mA; Imin. 40mA)
  • Quiescent current : 50mA (loop unloaded)
  • Max battery size and type : 2 x 12V 3.2Ah VRLA connected in series
  • No. of loop drivers : 1
  • Max. loop output current : 450mA (40V max)
  • Max. loop length : 1KM
  • Max. addressable devices per loop : 255
  • No. of conventional sounder circuits : 2 (Max. length per circuit is 500m)
  • EOL resistor value : 6800Ω 5% Tol. 0/25W (blue, grey, red, gold)
  • Max. sounder output current : 400mA
  • Auxiliary relays : 3 x Programmable Relays (programmable from C&Es). 1 x Fault Relay (active when no faults are
    present). Volt free single pole changeover. Max. switch current 1A; Max. switch voltage 30Vdc
  • Other outputs : 24V Aux. Power (19.5V min, 28V max). Protected by a resettable fuse. Max. current 100mA
  • Auxiliary inputs : 2 x Programmable Inputs (programmable from C&Es). Connect to 0V to trigger, Max. input voltage 27V
    (non-latching)
  • PC connection : PC connection via RS232 molex connector (supplied in XFP507 upload/download software kit); No printer
    connection available
  • Indicators : 2 line x 40 character backlit display; 16 Zonal LEDs, General Fire; Energised; Pre-Alarm; Remote Output
    Activated; Remote Output Disabled; Accessed; Disablement; Test; Silenced; General Fault; Syst
  • Connections : Fixed, largest acceptable conductor size 1mm2
  • Expansion connections :2-wire RS485 non-redundant network/repeater connection available via optional XFP761 network card.
    Max. 8 mains per network or 8 repeaters per non-networked main. Limit 1KM (main panel network) or
  • Product dimensions (mm) :380 W x 235 H x D 96mm (hole required for flush mounting = 367 W x 220 H x 75 D mm. No bezel
    required)
  • Construction & finish : Plastic lid and base; RAL7035 textured
  • IP Rating : IP30
  • Weight : 1.8kg (without batteries)
  • Operating conditions/temperature : -5ºC to +40ºC. Max relative humidity: 95%