Shopping Basket

0 Items

Subtotal £0.00

Fike CIE-A-400 2 Loop Addressable Fire Alarm Panel

£581.29 (inc VAT: £697.55)

Low Stock

SKU: 540-0001 Category: Brand:

Summary

The CIE-A-400 Addressable Fire Alarm Control Panel is a two loop panel capable of each loop supporting up to 200 devices* with a maximum loop length of 2KM. The panel also provides two configurable Monitored Input Circuits, 2 configurable Monitored Output Circuits, 2 configurable Relays, 1 Fault Relay and also a Peripheral Bus Circuit to add up to 8 Repeater Panels.

The system may be configured utilising 3 alarm stages with full ‘Zone to Zone’ Cause and Effect across all 32 panel zones with provision to include Alarm Confirmation and Delay Timers. An additional 32 output zones are also provided for more complex Cause and Effect programming.

The CIE-A-400 control panel is compatible with Fike’s addressable range of devices and utilises soft addressing principles eliminating the need for the installer to physically address each device whilst also eradicating time spent on faults caused by duplicate addressing. The operating parameters of the devices are configured either from the panel or via the OSP programming software and are then stored within the flash memory of the device itself. This enhanced digital protocol means less information is needed to be sent between the detector and the host control panel, resulting in faster, more reliable communication.

Cabinet installation

Surface mounting

At least three mounting holes provided in the back box should be used to secure the cabinet to a solid wall using suitable screws of at least 50mm in length. Ensure that a minimum gap of 50mm is left between the sides of the back box and any wall or projection (such as another box). 

Flush mounting 

An additional cradle (part number 23-0239) is available for use when flush mounting the panel. The cut out size for flush mounting is 362mm (W) x 338mm (H). When flush mounted the panel will sit at a depth of 83mm into cavity and have 36mm protruding from surface. 

Features

  • 2 loop Fike addressable panel.
  • Supports up to 400 devices.
  • 32 supported zones.
  • LCD display.
  • 31 character device labels.
  • 2000m max loop length.

Specifications

  • Maximum Number of Loops : 2
  • Max Loop Length : 2000m
  • Mains Supply Input : 230V AC Nominal
  • Standby Battery Requirement : 2 x 7/9Ah 12V Sealed Lead Acid (2 x 12/17Ah with extended battery box)
  • Max Conductor Resistance : 24 Ohms
  • Loop Loading : 450 DLU (200 Devices Max)
  • Loop Operating Voltage : 40V DC
  • Standby : 24V DC
  • Max Loop Current : 500mA
  • Number of Supported Zones : 32
  • LCD Display : LCD graphical display
  • Device Labels : 31 Characters
  • Event Log : 1,000 events
  • Repeater Panels : 8 Max
  • Aux Power Output : 30V DC 450mA
  • Inputs and Outputs :
    • Inputs : 2 x Monitored Inputs (3k3 EOL, 680R Firing Resistor)
    • Outputs : 3 x Volt Free Relay (30V DC @ 1A Max)
    • Monitored Outputs 2 x (32V DC @ 250mA Max, 10k EOL). Each monitored output may be configured as a Conventional Sounder Circuit, Fire Output or as a Common Fault Output.
  • IP Rating : IP30
  • Operating Temperature : +5°C to +40°C
  • Dimensions Panel (WxHxD) : 353x333x117mm

Downloads

Additional information

Weight 10 kg
Max Loops

Protocol

System Type

Touchscreen

Related Products