Hochiki FIRElink-100 2 Pipe Aspirating Smoke Detector with Docking Station

£1,446.36 (inc VAT: £1,735.63)

Low Stock

SKU: FIRELINK-100 Category: Brand:

Summary

Model FIRElink-100 is designed to provide very high sensitivity smoke detection in a small package. A unique sensing technology ensures that the detector operates at optimum sensitivity for the protected environment, without the need for complex setup. This means the product will configure itself to provide high sensitivity in a computer room or reduced sensitivity in a smoky area.

The detector is designed to fit into a Docking Station which accepts all sampling pipes and cables leaving the detector to be fitted during the final commissioning phase. This ensures that the detector is less likely to be damaged during installation.

Volt-free Fire 1 and Fault relay outputs are provided for remote monitoring by local fire detection or BMS systems

Features

  • Ultra small, low cost aspirating smoke detector for easy and discreet installation.
  • High sensitivity provided by laser based forward light scatter for reliable early warning.
  • Two sampling pipes up to 100 m (aggregate) in length (still air).
  • False alarms reduced by unique laser sensing technology – able to discriminate against dust.
  • RS485 communications built in as standard for networking and remote communications.

Specifications

  • Order Code : FIRElink-100
  • Supply Voltage : 21.6 – 26.4 V dc
  • Current Consumption : 400 mA @ 24 VDC
  • Relay Contact Rating : 500 mA @ 30 V
  • Operating Temperature Range : 0 to +38 °C (UL268), -10 to + 60 °C (CEA4022)
  • Operating Humidity Range : 0 – 90% non-condensing
  • Measurement Range (obs/m) :
    • 0.03% to 25% Full Scale Deflection (FSD)
    • 0.0015% to 25% Sensitivity Resolution
  • Detection Principle : Laser light scattering mass detection and particle evaluation
  • Particle Sensitivity Range : 0.003 μ to 10 μ
  • Dust Discrimination Principle : 3D3 Laser Dust Discrimination (LDD)
  • Maximum Sampling Pipe Length : 50m ( 2 x 25 m or 1 x 35 m) moving air (>1 ms) OR 100 m (2 x 50 m OR 1 x 65 m) still air (max)
  • Sampling Pipe Diameter : 3⁄4” nominal bore (27 mm O/D)
  • Alarm Levels : 2 – “FIRE” and “FAULT” (2 additional levels available with optional Relay Card or APIC fitted)
  • IP Rating : IP50
  • Sampling Pipe Inlets : 2
  • Exhaust Air Pipe Outlets : 1 (on optional Piped Exhaust docking station)
  • Weight(kg) / Size(mm) : 3.8 (with docking station) / H220 x W300 x D85