Hochiki Sav-Wire Manual Call Point
£8.36 (inc VAT: £10.03)
Summary
The CCP-SAVWIRE is a Sav-Wire call-point based upon the industry standard KAC world series housing and features easy to install, push-fit wiring terminals. The unit has been specifically designed for use on “Savwire” (two-wire) systems.
Features
- Designed for use on “Savwire” (two-wire) systems
- Approved to EN54-11:2001
- Terminals can accommodate up to a 2.5 mm² solid conductor
Specifications
- Ordering Code : CCP-SAVWIRE
- Nominal Operating Resistance : 470Ω
- Maximum Contact Resistance (R) : 200Ω
- Ingress Protection Rating : IP24D
- Operating Temperature Range : -10°C to + 55°C
- Storage Temperature Range : -10°C to + 55°C
- Maximum Humidity : 95%RH – Non condensing (at 40°C)
- Colour / Case Material : Red / ABS
- Weight (g) / Dimensions (mm) :
- Flush Mount : 110 / W89 x H93 x D27.5
- Surface Mount with Back Box : 160 / W89 x H93 x D59.5
Downloads
- Datasheet – (Adobe PDF)