ZFP Touchscreen Controlled Addressable CAST Fire Panel
£803.57 – £1,667.92
Summary
A feature-rich touchscreen-controlled addressable fire panel with 1, 2 or 4 C-Tec CAST compatible loop drivers.
Features
- A feature-rich touchscreen-controlled addressable fire panel with 1, 2 or 4 C-TEC CAST compatible loop drivers (see Key Features section for a full list of ZFP features).
- Third-party certified to EN54 parts 2, 4 and 13.
- Multiple off-the-shelf variants or build your own panel using our ZFP selection charts.
- Rapid loop learn, flexible cause & effects and powerful system diagnostics.
- Hi-integrity fault-tolerant RS485 networking option allows up to 128 network nodes (64 main panels and 64 Compact Controllers).
- Optional ‘A-Bus’ expansion PCBs, paging and graphic interface facilities.
- ENVISION Enabled – fullly compatible with C-TEC’s new Cloud based data management/remote access software
- Intuitive PC programming tools.
- Medium and large sized ZFPs also available with 2, 4, 6 or 8 loops.
Specifications
- Approvals/Certifications : Certified to EN54-2 & 4 by the LPCB. EN54-13 certification to follow
- Protocol/Compatibility : C-TEC CAST
- Mains Supply : 230V 50/60Hz
- Mains Rated Current : 1.3A maximum
- Internal Power Supply : 27Vdc nominal
- Total Output Current Limited To : 5A @ 230Vac
- Quiescent Current : Varies depending on the panel’s configuration – refer to our ZFP loop/battery calculation tool for details
- Battery Charge Capacity : 7Ah min to 18Ah max
- Max Battery Size & Type : 2 x 12V 18Ah VRLA connected in series
- Number Of Loop Drivers : 1, 2 or 4 (dependent on model purchased)
- Maximum Loop Output Current : 450mA
- Maximum Loop Length : 1km
- Maximum Addressable Devices Per Loop : 255
- Number Of Conventional Sounder Circuits : 2 (Max. length per circuit is 500m)
- EOL Resistor Value : 6800 5% Tol. 0/25W (blue, grey, red, gold)
- Maximum Sounder Output Current : 2 x 1A
- Auxiliary Relays :
- 2 x Programmable Relays (programmable from C&Es)
- 1 x Fault Relay (active when no faults are present)
- Volt free single pole changeover
- Max. switch current 1A; Max. switch voltage 30Vdc
- Other Outputs : 24V Aux. Power (19.5V min, 28V max). Protected by a resettable fuse. Max. current 100mA.
- Auxiliary Inputs : 2 x Programmable Inputs (programmable from C&Es). Connect to 0V to trigger, Max. input voltage 27V (non-latching).
- PC Connection : Via a galvanically isolated USB socket on the Z41 control module
- Pager/DECT Connection : RS232. ESPA compatible
- Graphics Interface/Diagnostics Connection : RS485. Drax compatible. C-TEC ENVISION Cloud Enabled.
- Network Connection : RS485 hi-integrity multi-path fault tolerant network connection via optional ZHN network card. Max 128 network nodes (up to 64 main panels & 64 compact controllers).
- Indicators : Full-colour 480 x 272 pixel touchscreen, all relevant EN54 indicators plus 5 programmable indicators. Additional indicators dependent on Switch & Indicator module fitted
- Controls : Interactive touchscreen with menu sensitive buttons; 1 x keyswitch allowing direct access to Access Level 2. Additional controls dependent on Switch & Indicator module fitted
- Connections : Fixed, largest acceptable conductor size 1mm2
- Expansion Connections : RS485 peripheral bus connection allows the connection of up to 15 ‘A-Bus’ PCBs (2 control cores plus screen plus 2 cores for power)
- Dimensions (WxHxD) : 450x462x127mm
- Construction & Finish : Light grey textured mild steel, 1.2mm Zintec. RAL7035 epoxy paint.
- IP Rating : IP30
- Operating Conditions/Temperature : -5°C to +40°C. Max relative humidity: 95%.
Downloads
- Datasheet (Adobe PDF)
Additional information
Weight | 10 kg |
---|---|
Loops | 1, 2, 4 |
Zone LEDs | 20, 40 |
Printer | No, Yes |